Mitsubishi Electric air conditioners are renowned for their whisper-quiet operation and reliability. However, like any advanced piece of technology, they can occasionally run into issues. When a fault occurs, the system’s self-diagnostic feature will display an error code on the wall controller or flash a specific LED sequence on the indoor unit.

Whether you are dealing with a simple blocked filter or a complex inverter communication fault, we have compiled the entire list of Mitsubishi Electric split system and ducted air conditioner malfunction error codes. Use our interactive tool or browse the tables below to determine the exact state of your air conditioning system.
Interactive Mitsubishi Error Code Lookup
Type your error code (e.g., P1, U8, 2502) into the search bar below to instantly diagnose the issue.
Mitsubishi Diagnostics Tool
Enter your 2-digit or 4-digit error code.
Mitsubishi Electric 4-Digit Error Codes
These precise 4-digit codes are commonly found on wired wall controllers for ducted and commercial systems.

| Error Code | Air Conditioner Fault Description |
| 0403 | Serial communication error |
| 1102 | Discharge temperature fault |
| 1301 / 1302 | Low pressure fault / High pressure fault |
| 1500 | Refrigerant overcharge |
| 2502 / 2503 | Drain pump fault / Drain sensor fault |
| 2600 | Water leak |
| 4116 | RPM error/Motor error |
| 4230 / 4260 | Heatsink overheat protection activated |
| 4240 / 4250 | Overload protection activated / Overcurrent protection activated |
| 4255 | Outdoor unit fan error |
| 5101 / 5102 | Temperature sensor fault / Return air thermistor fault |
| 6606 / 6607 | Communication fault / No ACK |
| 7100 / 7101 | Total capacity error / Capacity code setting error |
| 7130 | Incompatible unit combination |
Troubleshooting the Mitsubishi Electric 4-Digit Error Codes: Step-by-Step Guide
While alphanumeric codes are common on split systems, 4-digit error codes are typically found on wired remote controllers for ducted, multi-split, and City Multi commercial systems. These codes provide high-precision data about the system’s internal electronics and mechanical state.
Step 1: Diagnose Drainage & Water Issues (Codes 2500 – 2600)
- The Cause: Codes 2500, 2502, and 2503 indicate that the drain sensor is submerged or the drain pump has failed. Code 2600 is a direct alert for a water leak.
- The Fix:
- Check the drain pan for standing water. If full, the drain pipe is likely clogged with algae or slime.
- Clear the blockage using a wet/dry vacuum from the external discharge point.
- Pro Tip: If the code is 2503, the drain sensor itself may be faulty or disconnected.
Step 2: Address Pressure & Refrigerant Faults (Codes 1100 – 1500)
- The Cause: 1301 (Low Pressure) and 1302 (High Pressure) are the most frequent 4-digit faults. 1500 specifically indicates a refrigerant overcharge.
- The Fix:
- For 1302, ensure all supply vents are open and the return air filter is crystal clean. High pressure is often caused by heat being trapped in the fancoil.
- For 1102 (Discharge Temp), verify the outdoor unit has at least one meter of clearance for heat dissipation.
- Note: If these codes return after a filter clean, the system likely has a refrigerant leak or a faulty expansion valve.
Step 3: Power & Motor Synchronization (Codes 4100 – 4200)
- The Cause: These codes involve the “engine” of the unit. 4116 signals a fan motor error, while 4220 and 4225 indicate abnormal or low bus voltage.
- The Fix:
- Check your electrical DB box for a partially tripped breaker.
- For 4230/4260 (Heatsink Overheat), ensure the outdoor unit is not in direct, punishing sunlight during peak Penang or Singapore afternoons.
- Reset Procedure: Switch off the AC at the isolator for 15 minutes to reset the inverter power module.
Step 4: Resolve Communication & Addressing (Codes 6600 – 7100)
- The Cause: Found often in multi-unit setups, 6600 (Address Overlap) or 6607 (No ACK) mean the units aren’t “talking” to each other.
- The Fix:
- Check for loose wiring at the terminal block of both the indoor and outdoor units.
- If you recently added a new indoor unit, 7102 indicates the wrong number of units are connected to the outdoor condenser.
- Ensure the remote controller is properly assigned to the correct unit (Code 6201).
4-Digit Diagnostic Summary
| Error Code | Meaning | Severity |
| 0403 | Serial Communication Error | High |
| 1301 / 1302 | Low / High Pressure Fault | Critical |
| 2502 / 2503 | Drain Pump / Sensor Fault | Medium |
| 4116 | Indoor / Outdoor Motor Error | High |
| 5101 / 5102 | Temp Sensor / Return Air Thermistor Fault | Medium |
| 6607 / 6608 | No ACK / No Response | High |
| 7130 | Incompatible Unit Combination | Critical |
When is a Technician Required?
Because 4-digit codes often represent component-level failures, DIY fixes are limited to cleaning and resetting. You must call a professional if:
- Code 5101 – 5301: These involve testing the resistance of various thermistors and sensors.
- Code 6602: This indicates a hardware error in the transmission processor (PCB).
- Code 4250: This is an overcurrent protection trigger that could mean the compressor is failing.
Alphanumeric Codes (P-Series & E-Series)
Commonly seen on wall-mounted split systems, these codes indicate sensor anomalies and indoor/outdoor communication breakdowns.

| Error Code | Air Conditioner Fault Description |
| P1 | Intake sensor error / Abnormality of room temperature thermistor |
| P2 / P9 | Pipe (Liquid or 2-phase pipe) sensor error |
| P4 | Drain sensor error |
| P5 | Drain pump error / Malfunction of drain-up machine |
| P6 | Freezing/Overheating safeguard operation. Check for dirty air filter or damaged fan |
| P8 | Pipe temperature error / Damaged outdoor coil thermistor |
| E0 / E3 | Remote controller transmission error |
| E6 / E7 | Indoor/outdoor unit communication error (Signal receiving/transmitting error) |
| E9 | Indoor/outdoor unit communication error (Outdoor unit transmitting error) |
| EE / EF | Communication error between indoor and outdoor units / M-NET transmission error |
Troubleshooting the Mitsubishi P-Series & E-Series: Step-by-Step Guide
The P-Series and E-Series codes typically indicate issues with sensors, drainage, or communication between your indoor and outdoor units. While some of these require a technician to replace delicate electronic components, many can be addressed through proper maintenance.
Step 1: Resolve Airflow & Frost Issues (Code P6)
- The Cause: Code P6 is triggered by the freezing or overheating safeguard, often caused by a dirty air filter or a short air cycle.
- The Fix:
- Open the front panel and wash your return air filters with mild soap.
- Ensure there are no curtains or furniture blocking the airflow from the fancoil.
- Why it works: Restoring airflow allows the heat exchanger to maintain its proper temperature, automatically clearing the safeguard lockout.
Step 2: Check for Drain Blockages (Codes P4 & P5)
- The Cause: P4 indicates a drain sensor error, while P5 signals a malfunction in the drain pump or overflow mechanism.
- The Fix:
- Check if water is dripping from the unit; this confirms the drain is backed up.
- Inspect the external drain pipe (usually leading to a toilet or floor trap) for slime or algae clogs.
- Expert Tip: If you have a ducted system, ensure the drain sensor hasn’t become submerged due to a tilted unit.
Step 3: Verify Remote & Signal Integrity (Codes E0 – E5)
- The Cause: These codes indicate transmission errors or receiving faults between your remote controller and the main board.
- The Fix:
- For wireless remotes, replace the batteries with fresh alkaline ones.
- For wired controllers, check for “bad contact” in the transmission wire.
- Interference Check: Ensure no new high-frequency electronic appliances (like high-powered routers or induction cookers) have been placed directly under the AC, as noise waves can cause signal errors.
Step 4: The Communication Reset (Codes E6, E7, & EE)
- The Cause: These are critical communication errors between the indoor and outdoor units.
- The Fix:
- Perform a “Hard Reset.” Switch off the AC isolator switch (located near your outdoor condenser) for 10 full minutes.
- Turn the power back on and wait 3 minutes before starting the unit.
- Warning: If the code returns immediately, there may be a miswiring or a burnt communication chip on the PCB.
P & E Series Diagnostic Summary
| Error Code | Meaning | Primary Location to Verify |
| P1 / P2 | Intake or Pipe Sensor Error | Bad contact or damaged thermistor |
| P5 | Drain Pump Malfunction | Clogged drain line or faulty pump |
| P6 | Freezing / Overheating | Clean air filters immediately |
| E6 / E7 | Comms Error (Indoor/Outdoor) | Check connecting signal wires |
| E0 / E3 | Remote Transmission Error | Bad contact or remote board fault |
When to Call the Pros?
If a Hard Reset and Filter Cleaning do not clear the code, the issue is likely a component failure.
- For Sensor Faults (P1, P2, P4, P9): These usually require a technician to test the thermistor’s resistance and replace the part if it is damaged.
- For Board Faults (Fb, E1, E2): These indicate internal control system or memory errors that require a PCB repair or replacement.
Compressor and Power Faults (U-Series & F-Series)
These faults represent critical power interruptions, high pressure, or compressor-related safety cut-offs. Professional diagnosis is highly recommended.

| Error Code | Air Conditioner Fault Description |
| U1 / Ud | Abnormal high pressure / Overheating safeguard operation |
| U2 | Abnormal high discharging temperature / Insufficient refrigerant |
| U3 / U4 | Open/short of outdoor unit thermistors |
| U6 | Compressor overcurrent interruption / Abnormal power module |
| U8 | Outdoor unit fan safeguard stop |
| UF | Compressor overcurrent interruption (When compressor locked) |
| F1 / F2 | Reverse phase detection / L3 open phase detection |
| F9 | Connector 2 or more open |
Troubleshooting the Mitsubishi U-Series & F-Series: Step-by-Step Guide
The U and F Series codes represent critical system protections and power-related faults. These errors often trigger a safety shutdown to protect the compressor and electrical modules from permanent damage. While these codes frequently require a technician’s multimeter, you can perform several preliminary checks to narrow down the cause.
Step 1: Inspect the Outdoor Condenser (Codes U1, U2, U8)
- The Cause: These codes signal abnormal high pressure, high discharge temperatures, or a fan safeguard stop. This is often due to the system’s inability to “breathe” or dissipate heat.
- The Fix:
- Check for any obstructions around the outdoor unit, such as overgrown plants, stored boxes, or laundry.
- Ensure the outdoor fan blades are not physically jammed by debris.
- Why it works: Clearing the area around the condenser allows for proper heat radiation, which can resolve U2 (overheating) or U8 (fan stop) issues.
Step 2: Check Power & Phase Stability (Codes U9, UH, F1, F2)
- The Cause: U9 and UH indicate overvoltage, voltage shortages, or current sensor errors. F1 and F2 specifically point to “Reverse Phase” or “Open Phase” detection, meaning the electricity isn’t flowing correctly into the unit.
- The Fix:
- Verify your main circuit breaker is fully engaged and hasn’t partially tripped.
- If you have recently had electrical work done at your home, the F1 code may indicate that the power phases were wired in reverse.
- Warning: Power and phase issues involve high voltage; if the breaker continues to trip, do not attempt to force it back on.
Step 3: Verify Refrigerant Levels (Code U2)
- The Cause: Beyond overheating, U2 can explicitly indicate “insufficient refrigerant”.
- The Fix:
- Look for signs of a leak, such as oily residue on the copper pipe joints or ice forming on the indoor cooling coils.
- If the unit was recently installed, ensure the ball valves were fully opened by the installer.
- Note: If the gas is low, a professional “pressure test” is required to find the leak before topping up the refrigerant.
Step 4: Perform a Deep System Reset
- Because U and F codes often involve the “Power Module” or “Inverter Heatsink”, a standard remote reset is rarely enough.
- The Fix: Switch off the main power at the isolator or DB box for at least 15 minutes. This allows the internal power capacitors to drain completely and resets the error log on the main PCB.
U & F Series Diagnostic Summary
| Error Code | Meaning | Severity |
| U1 / Ud | Abnormal High Pressure / Overheating | High |
| U2 | High Discharge Temp / Low Refrigerant | High |
| U8 | Outdoor Fan Safeguard Stop | Medium |
| U9 / UH | Overvoltage / Voltage Shortage | High |
| F1 / F7 | Reverse Phase / PCB Circuit Fault | Critical |
| F3 / F4 | Connector Open (63L or 49C) | Medium |
When to Call a Professional?
If the F-Series or U-Series codes persist after a deep reset, the system has detected a genuine hardware failure that DIY checks cannot resolve.
- For F1/F2/FA: These require a technician to verify the incoming power phases and inspect the Reverse Phase Detection Circuit on the PCB.
- For U3/U4: These indicate a short or open circuit in the outdoor thermistors, which must be tested with a multimeter and replaced.
- For U6/UF: These signal a compressor overcurrent or a locked compressor, often requiring a new start-up capacitor or, in severe cases, a compressor replacement.
Mitsubishi Air Conditioner Troubleshooting FAQ
Need Expert Mitsubishi AC Repairs?
Whether it is a P5 drainage fault, a flashing LED, or a unit that won’t power on, our experienced technicians can diagnose and fix your Mitsubishi Electric system efficiently.